The Engineering
Advisor is intended to enhance your knowledge of technical issues relating to
buildings. For additional information on any subject, please feel free to call
us. Our commitment is to provide you with timely, accurate information.
|
COOLING TOWERS |
Cooling towers are installed next to, behind, or on top of large buildings to remove heat from water used in a chilled water mechanical refrigeration (air conditioning) system. The concept is simple, akin to perspiration. Latent heat of vaporization is removed from the water by blowing air over it. Typically, the temperature of the water is reduced by about 10 degrees F. before it returns to the refrigeration system. |
|
Cooling Tower Maintenance Issues
|
Though simple
devices, cooling towers require routine maintenance to perform optimally.
Preventive maintenance should include: Water Treatment
and Corrosion Control: All cooling towers must have water treatment systems for the
prevention of biological and chemical degradation of the equipment.
Biologicals that can exist in a tower basin are legionella, dead
animals, and algae. Chemicals that can build up in a tower basin or on tower
wet surfaces are rust, residues from hard water, residues from chemical
treatments (if not properly administered), and residues from rain. Sediments
can also build up from windblown dirt and plant matter. Freezing protection
is often a challenge for cooling towers that must run in the winter. Water treatment for
biologicals and rust is generally done automatically by a time-based chemical
injector system (small pump and timer piped into the condenser water system)
or manually by adding premixed chemicals through a small tank. Sediment is
usually caught in strainers or settles in the basin and must be manually
flushed out. Freeze protection is
accomplished by electric heaters in the pan or basin of the tower. Heaters
generally aren’t operated while the tower is in use. The heat being rejected
by the tower keeps the pan from freezing. You may see water freeze up on the
"fill" or inside surfaces of the tower in winter. This can destroy
the inner surfaces of the tower if not addressed. Freeze protection is very
often in the piping to the tower as well. Heating cable is usually wrapped
around the piping to and from the tower and then insulated. Fan
Motors/Bearings:
Tower fans come in a variety of styles. Fan speed or quantity is used to
control the temperature of the water leaving the tower, which is critical for
the efficient operation of the chiller plant. Where there are multiple
motors, they may be directly connected to a fan via the motor shaft or
gearbox, or they may drive a fan through a belt drive. Gearboxes are pretty
rugged, and maintenance on these is just like that for your car: check the
oil. Belt drives are subject to a lot of wear and tear due to multiple starts
and stops as well as weathering. Bearings also are exposed to the weather
constantly and require regular checks for washed-out grease. Cleaning: Most towers, except for winterized units, are shut down during the cooler weather (50 degrees and less). The tower will stay off until the warm weather returns. Just before this happens, the tower should be cleaned out and checked. The basin should be filled and checked for leaks that may have formed in the off-season, dirt that may have accumulated, and fill that may have been damaged by the weight of ice. |
|
What We Inspect
|
When asked to
perform a Property Condition Assessment, our review of building system
components is necessarily limited. However, there are a number of things we
do look at to help determine whether the system has been well maintained,
whether the system is performing as intended, whether there are any safety
concerns, and how future maintenance, repair, or replacement has been anticipated.
The things we look at include: Base and Mounts We look for:
Noise and
Vibration
When a tower is running, it should be pretty quiet. Noise will be produced
when:
Size v.
Anticipated Load
The cooling tower should be able to reject at least as much heat as
the chiller plant can transfer to it. If a tower is not sized properly, it
would be discovered long before a PCA was done. A tower’s ability to reject
heat is based on its ability to evaporate water. If a tower has all fans running
and the leaving water temperature is not 10 to 12 degrees cooler than the
entering water, there may be a loss of capacity. Cleanliness, proper water
distribution inside, damaged fill, loose belts, or failed fan motors are
potential culprits. When inspecting, we look for the steadiness of the fan
speed. Speed fluctuations over a period of a few minutes reflect an
out-of-tune control system or problems in flow control. Evidence of
Corrosion
We inspect for:
Overspray Overspray is caused by either
too much air blowing through the tower and taking the water droplets with it
or the entering water not being properly distributed on the cooling surfaces
of the tower. Overspray can be felt by people entering or leaving the
building, or the overspray carries water treatment chemicals that cause spots
on parked cars. If the tower is otherwise okay, it’s possible to install
screening over the discharge of the tower to break up the water droplets.
Overspray is situational. You may not see it on a particular day because the
tower is lightly loaded and only one fan is running at a low speed. Makeup water As towers evaporate water to
produce cooling, water needs to be made up from the building’s city
connection. In the tower basin/pan, there is usually a level control, like in
a toilet tank, that keeps a certain amount of water in the system at all
times. These devices can get stuck, corroded, or fouled. Water can be
constantly running into the pan, through the overflow and out to the storm
drains. This wastes treatment chemicals and water and could bring on
environmental penalties. |
|
Repair or Replace
|
When a
cooling tower is old, consideration must be given to how long it can remain
in service before maintenance costs exceed replacement costs. Fortunately, there aren’t a
lot of moving parts in a tower. With proper maintenance, a tower can last up
to 20 years. When repairs are needed, they are generally on motors, bearings,
belts, controls, and gaskets. These repairs are all reasonable, but when a
tower goes for long periods without corrosion and water treatment, the major
structure of the tower begins to decay. Replacement of a tower requires
electrical, mechanical, and rigging trades; downtime; permits; and plan
review by the local authority. If the tower is on a roof, the rigging and
permit process gets worse. If a helicopter is required and you’re near an
airport, the FAA is also involved. It’s always advisable to try and repair
the tower in place, even for major repairs. A new tower will cost about
$50/ton (capacity) plus installation. Rebuilding can be more cost -effective,
especially if sections of the tower can stay online while sections are being
rebuilt. There are firms that specialize in this service. Criterium Engineers
can help you find and work with these firms. |
|
|